Peace of Mind Generators · Technician Tool

Load Calculation Analysis

Residential 120/240 V, single-phase selected-load analysis with fuel-specific Generac sizing.

v1.2.1
Planning analysis: Enter actual nameplate ratings whenever available. This tool is not a final service, feeder, transfer-switch, fuel-system, or permit calculation.
1

Customer & location

Identify the residence and select the proposed fuel.

2

General lighting & receptacle load

Enter the property area. The application calculates conditioned area and applies the residential general-load demand method automatically.

Garage area allowance 250 ft² 1 × 250 ft² per garage
Conditioned home area 0 ft² Gross area − garage allowance
General load before demand 0 VA 3 VA/ft² + required small-appliance and laundry allowances
NEC-adjusted general load 0 VA First 3,000 VA at 100%; qualifying remainder at 35%
3

High-load appliances & equipment

Select quantity and how the load will operate during an outage. Nameplate details remain available only when field verification is needed.

4

Essential appliances & motor loads

Add only equipment intended to operate during the outage.

5

Other / custom loads

Add field-verified loads not shown above.

No custom loads added.

6

Calculation & recommendation

Generator kW is selected from NEC-adjusted continuous served load. Motor starting is reviewed separately.

NEC-adjusted general load 0.0 kW Includes dwelling demand factor
Generator-served calculated load 0.0 kW Selected loads after applicable demand factors
Load-control exclusion 0.0 kW No managed or locked-out loads
Continuous sizing target 0.0 kW Includes internal planning margin
Motor-start review Complete the load selection
Starting demand does not automatically increase continuous generator kW.
Complete required inputs

Recommended system

Enter home square footage and select the intended loads.

Fuel-rated output
Rated current
Main breaker
Estimated utilization
Required controls
Without load controls
Methodology, assumptions & source notes
  • Conditioned area equals gross home area less 250 ft² per selected garage space.
  • General load includes conditioned area at 3 VA/ft², two 1,500 VA small-appliance circuit allowances, and one 1,500 VA laundry allowance. The first 3,000 VA is calculated at 100% and the qualifying remainder at 35%.
  • Four or more eligible fixed appliances receive the 75% dwelling demand factor automatically. Dedicated cooking, drying, HVAC, heating, EV, and other noneligible loads remain outside that factor.
  • Runs on Generator loads are included. SMM Managed loads are initially shed and may remain unavailable. Locked Out loads are unavailable for the entire outage. Both controlled modes are excluded from the primary continuous recommendation.
  • Generator kW is selected from NEC-adjusted continuous served load plus the administrator-set planning margin. Motor starting is a separate review and does not automatically become continuous generator kW.
  • HVAC Soft Start reduces estimated LRA by 60% for the internal starting review; running VA is unchanged. Enter actual nameplate LRA under Edit nameplate when available.
  • Gaseous model selection uses published LP and NG ratings separately. NG output can be lower than the generator’s marketed kW designation.
  • Houston, TX Metro assumptions are fixed at 50 ft elevation and 100°F planning ambient. Gaseous output is adjusted using Generac’s published rating note; diesel derating remains product-specific.